CityView Portal

Permit Application Status

PRSF240344


You will only be able to schedule inspections if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRSF240344
New Single Family Dwelling
Permit(s) Issued
INGRAM, MATTHEW G & O'ROURKE, KARENA M (JT)
New
R-3 - Residential, one- and two-family
New Single Family Dwelling 3 Bedroom, 3.5 Bathroom 3800 Ft² Finished, 833 Ft² Unfinished
04/23/2024
05/09/2024

Locations

Submittals

1 Permit Application Submittal 04/23/2024      Status: Returned for Correction

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Fire Code Review Failed 05/07/2024 05/09/2024
Bob Reilley ((970) 736-8104)   Send Email
A.) Applicant will need to include with the building plans a site plan showing the full length and width of the driveway to the residence and indicating the slope and grade for the proposed access. If necessary, turn arounds and turn outs must be clearly identified. B.) OCFPD will need to be able to stretch 2 150’ around the residence and have them meet. Because of the perimeter distance of the structure, residence will most likely need to be sprinklered. See Fire District website for more information. C.) Permit Fees must be paid to Oak Creek Fire Protection District. Please see Fire District website for more information. The Fee of $596.60 {1,000,000 [549.80] + 360,000 [46.80]} must be received prior to permit approval. Please deliver fee by check to: Oak Creek Fire Protection District PO Box 152 Oak Creek, CO 80467 [Bob Reilley @ 05/05/2024 11:37 AM] [Bob Reilley @ 05/05/2024 11:32 AM] Applicant has submitted driveway plan showing acceptable length, width, slope and turnaround at residence. Permit Fees have been paid to Oak Creek Fire Protection District. Please be aware that OCFPD will need to be able to stretch 2 150’ around the residence and have them meet. If this is not accomplished because of the perimeter distance of the structure, residence will need to be sprinklered before a CO/TCO will be issued. See Fire District website for more information. [Bob Reilley @ 05/09/2024 12:03 PM]
Environmental Health Review Approved 05/07/2024 05/07/2024
Christopher Peters ((970) 870-5354)   Send Email
OWTS pemit #PRSP240210 has been issued, See conditions [Christopher Peters @ 05/07/2024 9:31 AM]
External Agencies Review Approved 05/07/2024 05/07/2024
Todd Carr ((970) 870-5330)   Send Email
Morrison Creek Water and Sanitation The property is larger than 5 acres The district does not serve this property. Approved by the district YVEA - inspections@yvea.com The applicant has already been working with YVEA on a electrical design on the property.
Public Works Review Failed 05/07/2024 05/06/2024
Tony Brown ((970) 870-5344)   Send Email
Cut and fill amounts need to be shown for driveway construction to determine if a Construction, Storm Water, Grading and Excavating permit will be required.
Building Code Review Failed 05/07/2024 05/06/2024
Ted Allen ((970) 870-5329)   Send Email
See Document Markups
Carried Forward
05/09/2024


RCRBD has adopted the 2021 IRC with Appendix F Radon passive radon gas control system per IRC AF103 on new single Family homes – installation of passive submembrane depressurization system is required under one-family dwelling and shall be indicated in the approved design drawings.
Miscellaneous
Carried Forward
05/09/2024


RCRBD has also adopted the State of Colorado Model Electric and Solar Ready Code. Details shall include, but are not limited to, the following as applicable: Electrical capacity, appropriately phased branch circuit sized to accommodate future electric equipment and reserved physical space for circuit breakers in the main panel that are properly labeled.
Miscellaneous
Carried Forward
05/09/2024


The Building Department would allow a deferred submittal on the Stamped Electrical Engineers Plans, see the Routt County Regional Building Department Policy requirements for dwellings that will have a 400 AMP Service or Larger, if applicable. I have also set conditions for deferred heat load calculations, and blower door test to be completed. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACCA Manual J.
GIS Land Development Review Approved 05/07/2024 04/25/2024
Lauren Wade ((970) 870-5465)   Send Email
Address assigned: 23620 Fraysher Ln Oak Creek, CO 80467
Planning Review Approved 05/07/2024 04/24/2024
Michael Fitz ((970) 879-2704)   Send Email
Single-family home proposed on Lot 3 Ski View Estates. Setbacks (building envelope), height, waterbody setbacks, skyline OK. No other Planning concerns.

2 Permit Application Submittal 05/07/2024      Status: Pending

Review Type Outcome Est. Completion Date Completed
Fire Code Review Approved 05/15/2024 05/09/2024
Bob Reilley ((970) 736-8104)   Send Email
Applicant has submitted driveway plan showing acceptable length, width, slope and turnaround at residence. Permit Fees have been paid to Oak Creek Fire Protection District. Please be aware that OCFPD will need to be able to stretch 2 150’ around the residence and have them meet. If this is not accomplished because of the perimeter distance of the structure, residence will need to be sprinklered before a CO/TCO will be issued. See Fire District website for more information. [Bob Reilley @ 05/09/2024 3:07 PM]
Building Code Review Approved 05/15/2024 05/09/2024
Ted Allen ((970) 870-5329)   Send Email
See Document Markups
Resolved
05/09/2024


RCRBD has adopted the 2021 IRC with Appendix F Radon passive radon gas control system per IRC AF103 on new single Family homes – installation of passive submembrane depressurization system is required under one-family dwelling and shall be indicated in the approved design drawings.
Miscellaneous
Resolved
05/09/2024


RCRBD has also adopted the State of Colorado Model Electric and Solar Ready Code. Details shall include, but are not limited to, the following as applicable: Electrical capacity, appropriately phased branch circuit sized to accommodate future electric equipment and reserved physical space for circuit breakers in the main panel that are properly labeled.
Miscellaneous
Resolved
05/09/2024


The Building Department would allow a deferred submittal on the Stamped Electrical Engineers Plans, see the Routt County Regional Building Department Policy requirements for dwellings that will have a 400 AMP Service or Larger, if applicable. I have also set conditions for deferred heat load calculations, and blower door test to be completed. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACCA Manual J.
Public Works Review Approved 05/15/2024 05/09/2024
Tony Brown ((970) 870-5344)   Send Email

Fees

Paid Fees Amount Paid Owing Date Paid
Routt County Use Tax Fee $6,800.00 $6,800.00 Paid 05/09/2024
Routt County Planning Dept Plan Review Fee $75.00 $75.00 Paid 04/23/2024
Building Permit Fee $5,050.38 $5,050.38 Paid 05/09/2024
Plan Review Fee $3,282.75 $3,282.75 Paid 04/23/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Framing Inspection Pending
Wall/Roof Sheeting Pending
Roofing Inspection Pending
Shower Pan Inspection Pending
Drywall Inspection Pending
Grading Inspection Pending
Mike Mordi   Send Email
Final Grading Inspection Pending
Tony Brown ((970) 870-5344)   Send Email
Lath/Veneer Inspection Pending
Building Final Inspection Pending
Structural Inspection Pending
Footing Inspection Pending
Foundation Inspection Pending
Insulation Inspection Pending
Footing Inspection Partial Pass 5/9/2024 (AM) 5/10/2024 05/15/2024
Jeff Yeiser ((970) 870-5371)   Send Email
Foundation Inspection Partial Pass 5/17/2024 5/17/2024 05/17/2024
Jeff Yeiser ((970) 870-5371)   Send Email
Foundation Inspection Partial Pass 5/21/2024 5/21/2024 05/21/2024
Jeff Yeiser ((970) 870-5371)   Send Email
Foundation Drain Inspection Passed 6/10/2024 06/10/2024
Jeff Yeiser ((970) 870-5371)   Send Email
Foundation Water Proofing Passed 6/10/2024 06/10/2024
Jeff Yeiser ((970) 870-5371)   Send Email
Foundation/Underslab Insulation Passed 7/23/2024 7/23/2024 07/23/2024
Jeff Yeiser ((970) 870-5371)   Send Email
Radon Piping Passed 7/23/2024 7/23/2024 07/23/2024
Jeff Yeiser ((970) 870-5371)   Send Email
Insulation Inspection Partial Pass 7/24/2024 7/24/2024 07/24/2024
Jeff Yeiser ((970) 870-5371)   Send Email

Conditions

Condition Status Department Category Expiration Date Due Date
Final Fire Inspection Required Open Prior to Issuance of TCO/CO/CC
: Final Fire Inspection Required 1. Address sign may be posted on house (if closer than 50' from roadway and is clearly seen from roadway) or posted at the entrance of the roadway. Sign must be aluminum with reflective vinyl for background and lettering. Lettering must be at least 4" in height and white in color. Background must either be green, brown, or blue. Sign can be either horizontal or vertical. The installation of the sign must be permanent and able to withstand weather and be high enough off the ground so that it remains visible during winter snowpack. See www.oakcreekfire.org for more information. 2. Propane tank (if applicable) must have a grey schedule 40 3/4" PVC pipe permanently mounted at the location of the tank’s shutoff valve. Pipe must be long enough to see during winter snowpack. See Fire District website for more information. 3. If the Property has a reporting fire alarm system, an Oak Creek Fire Knox box must be permanently mounted on either garage side or front of the house at an approved location. Knox Box must be keyed to the Oak Creek Fire Protection District. See Fire District website for more information. Questions - please email permits@oakcreekfire.org [Bob Reilley @ 05/05/2024 11:38 AM]
Design Engineer on-site Wastewater final report Open Environmental Health Prior to Issuance of CO/CC
: Design Engineer on-site Wastewater final report, including as Built drawing. [Christopher Peters @ 05/07/2024 9:29 AM]
Blower door test results Open Building Services Prior to Issuance of CO/CC
: Blower Door Test Results [Ted Allen @ 05/09/2024 9:39 AM]
Heat Loss Calculations Deferred Submittal Open Building Services Prior to Mechanical Permit Issuance for Heat
: Heal Load Calculations must be submitted, reviewed and approved prior to any heating equipment being installed. [Ted Allen @ 05/09/2024 9:39 AM]

Related Permit & Planning Applications

Reference Number Status Type
PREL240676 Permit(s) Issued Electrical
PRPL240679 Permit(s) Issued Plumbing
PRMH240830 Permit(s) Issued Mechanical
PRGS240937 Permit(s) Issued Gas

Documents & Images