PRAD220504


You will only be able to schedule inspections if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRAD220504
Addition
Permit(s) Issued
David Fisher
Addition
Add a 3-car garage with a bonus room above it.
05/10/2022
04/21/2023
04/21/2026

Locations

Submittals

1 Permit Application Submittal 05/10/2022      Status: Returned for Correction

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
GIS Land Development Review Approved 07/13/2022 07/13/2022
Jason Blair ((970) 870-5465)   Send Email
Public Works Review Approved 07/13/2022 07/11/2022
Tony Brown ((970) 870-5344)   Send Email
Building Code Review Failed 07/13/2022 07/07/2022
Malea Michael-Ferrier ((970) 870-5334)   Send Email
See Document Markups
Carried Forward
11/01/2022


Sheet F2, details 1-4 have notes referring to the soils report: Please provide soils report.
Miscellaneous
Carried Forward
11/01/2022


Sheet A4: Detail 4 refers to the soils report, please submit soils report or spell out in the note what is being done.
Egress
Carried Forward
11/01/2022


Sheet A3: Dwellings shall be provided with a means of egress in accordance with R311.1. The means of egress shall provide a continuous and unobstructed path of vertical and horizontal egress travel from all portions of the dwelling to the required egress door without requiring travel through a garage. The required egress door shall open directly into a public way or to a yard or court that opens to a public way. Please add a door to the exterior per R311.1 Means of egress and resubmit.
Miscellaneous
Carried Forward
11/01/2022


Sheet A3: Stairs at bunk beds to be considered furniture and not permanent. This is not a legal staircase.
Miscellaneous
Carried Forward
11/01/2022


Sheet A3: What type of fuel is being used for the fireplace?
Fire Code Review Approved 07/13/2022 07/06/2022
Doug Shaffer ((970) 871-8612)   Send Email
Full Permit. NB
Environmental Health Review Approved 07/13/2022 07/05/2022
Amanda Williams ((970) 870-5588)   Send Email
Not applicable to RCEH project is on Timber's W&S
Planning Review Failed 07/13/2022 06/28/2022
Michael Fitz ((970) 879-2704)   Send Email
Miscellaneous
Carried Forward
11/01/2022


Please record new subdivision plat.
Plat for project PL20210025/TPL-20-172 has not been recorded yet. Planning cannot review unless there is a recorded plat to review against. An email was sent on 6/21/2022 to fisher78701@yahoo.com, the contact for project TPL-20-172, inquiring about the status of the replat, with no response as of 6/28/2022. NOTE - site plan appears to show the existing building envelope. While this is correct at the moment, the envelope will change when the plat is recorded, and that will result in a Correction to revise the site plan. Please be aware.

2 Permit Application Submittal 07/15/2022      Status: Pending

Review Type Outcome Est. Completion Date Completed
Building Code Review Approved 11/08/2022 11/03/2022
Malea Michael-Ferrier ((970) 870-5334)   Send Email
See Document Markups
Resolved
11/03/2022


Sheet F2, details 1-4 have notes referring to the soils report: Please provide soils report.
Miscellaneous
Resolved
11/03/2022


Sheet A4: Detail 4 refers to the soils report, please submit soils report or spell out in the note what is being done.
Egress
Resolved
11/03/2022


Sheet A3: Dwellings shall be provided with a means of egress in accordance with R311.1. The means of egress shall provide a continuous and unobstructed path of vertical and horizontal egress travel from all portions of the dwelling to the required egress door without requiring travel through a garage. The required egress door shall open directly into a public way or to a yard or court that opens to a public way. Please add a door to the exterior per R311.1 Means of egress and resubmit.
Miscellaneous
Resolved
11/03/2022


Sheet A3: Stairs at bunk beds to be considered furniture and not permanent. This is not a legal staircase.
Miscellaneous
Resolved
11/03/2022


Sheet A3: What type of fuel is being used for the fireplace?
This is not approved as a secondary unit but as a living space that is part of the main residence. If, in the future, someone wants to make this a secondary unit, then the garage and unit must be separated with a 1 hr fire rated assembly, as well as the garage walls supporting the unit.
Planning Review Approved 11/08/2022 11/02/2022
Michael Fitz ((970) 879-2704)   Send Email
Miscellaneous
Resolved
11/02/2022


Please record new subdivision plat.
Resolution (PUD amendment) recorded at Reception #841973 and plat recorded at Reception #841974. Per discussion with staff, this space is OK whether it is a dwelling unit or not. If it's merely a bonus room, then it's just a bonus room. If it later becomes a dwelling unit, that is OK per the PUD, which specifies up to 13 units allowed on lot 4.

Fees

Paid Fees Amount Paid Owing Date Paid
Routt County Use Tax Fee $3,500.00 $3,500.00 Paid 04/20/2023
Routt County Planning Dept Plan Review Fee $75.00 $75.00 Paid 06/03/2022
Steamboat Springs Fire Department: Plan Review Fee $25.00 $25.00 Paid 04/20/2023
Building Permit Fee $3,145.78 $3,145.78 Paid 04/20/2023
Plan Review Fee $2,044.76 $2,044.76 Paid 06/03/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection Pending
Foundation Inspection Pending
Foundation Drain Inspection Pending
Framing Inspection Pending
Roofing Inspection Pending
Insulation Inspection Pending
Drywall Inspection Pending
Grading Inspection Pending
Mike Mordi   Send Email
Final Grading Inspection Pending
Tony Brown ((970) 870-5344)   Send Email
Building Final Inspection Pending
Structural Inspection Pending
Foundation Water Proofing Pending
Foundation/Underslab Insulation Pending
Lath/Veneer Inspection Pending
Radon Piping Pending
Shower Pan Inspection Pending
Wall/Roof Sheeting Pending

Conditions

Condition Status Department Category Expiration Date Due Date
Truss Drawings Deferred Submittal Open Building Services Prior to Insulaton Inspections Scheduled
: Truss drawings shall be submitted, reviewed and approved prior to installation and inspections.