Permit Application Status
PRAD250104
You will only be able to schedule inspections if you are a contact on the permit application.
Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.
Summary
Property Owner's Full Name:
Locations
Submittals
1 Permit Application Submittal 02/24/2025
Status: Returned for Correction
Documents Returned For Corrections
Review Type
Outcome
Est. Completion Date
Completed
Environmental Health Review
Failed
03/19/2025
03/17/2025
Reviewer:
Reviewer Comments:
All structure are not shown on site plan. Please show all existing structures. ISDS (septic) permit was issued in 1977 for a three bedroom home. The addition of the new primary suite will increase the calculated waste water flows from the residence beyond the capacity of the 1977 system. A professional engineer, licensed pumper, and RCDEH must be onsite at the same time to pump and inspect the nearly 50 year old septic system before granting approval. An new OWTS (septc) system may be required to bring the property into compliance with state septic regualtions. [Christopher Peters @ 03/17/2025 10:28 AM]
Public Works Review
Failed
03/19/2025
03/17/2025
Reviewer:
Reviewer Comments:
Unable to approve with current site plan. Please show current driveway length, width and grade.
Building Code Review
Approved
03/19/2025
03/11/2025
Reviewer:
Reviewer Comments:
Major addition is defined as an addition that is greater than 50% of the existing building square footage. Details in approved plans include, but are not limited to location of EV space and EV Supply Equipment (as applicable) electrical capacity and reserved physical space for circuit breakers in the main electrical service panel that are properly labeled with each type for the solar-ready zone, from location of the parking space for Electric Vehicle and unless HVAC is electric similar consideration (as applicable) from location of the panel to Electric receptacle or junction box within 3 feet of the combustion equipment or appliances per RE301.1 General. [Ted Allen @ 03/11/2025 1:43 PM]
Planning Review
Failed
03/19/2025
03/10/2025
Reviewer:
Corrections:
Correction 1:
Miscellaneous
Comments:
All structure are not shown on site plan. Please show all existing structures and if within the setback indicate how legal status was obtained.
Reviewer Comments:
All structure are not shown on site plan. Please show all existing structures and if within the setback indicate how legal status was obtained. If encroachments are illegal, then an addendum to demo these structures will be needed before TCO from planning.
Setback- the addition is OK (Outbuildings maybe in setback)
Height- OK
Water Body- OK
Skyline- new addition is same height as existing house and on the opposite side of RCR14- no need for a new skyline test
Use- Single Family Dwelling
Size Limit- OK
Fire Code Review
Failed
03/19/2025
03/08/2025
Reviewer:
Corrections:
Correction 1:
Miscellaneous
Comments:
Resubmittal of site plan required - resubmittal of site plan with access width, grade, turning radius and turnaround meeting Fire Dept. access requirements. If unable to meet requirements, submittal of fire sprinkler and monitored fire alarm plans and permits. No inspections past foundation until the above is resolved. www.steamboatsprings.net for details. [Matt Workman @ 03/10/2025 9:36 AM]
Reviewer Comments:
Resubmittal of site plan required - resubmittal of site plan with access width, grade, turning radius and turnaround meeting Fire Dept. access requirements. If unable to meet requirements, submittal of fire sprinkler and monitored fire alarm plans and permits. No inspections past foundation until the above is resolved. www.steamboatsprings.net for details. MW 3-8-25
GIS Land Development Review
Approved
03/19/2025
03/07/2025
Reviewer:
Reviewer Comments:
No addressing changes needed.
2 Permit Application Submittal 03/17/2025
Status: Pending
Review Type
Outcome
Est. Completion Date
Completed
Environmental Health Review
Approved
03/28/2025
03/28/2025
Reviewer:
Reviewer Comments:
RCDEH was onsite to inspect the OWTS on 3/28/2025. The septic is located in the general area indicated in the permit. The system was originally constructed to handle 3 bedrooms. The current home is one bedroom expanding to 2 bedrooms. Nordic pumping conducted a full NAWT type inspection in 2019 and pumped the tank again in 2023. Nordic reports the system is in good working order. No signs of effluent surfacing or tank failure was observed during the 3/28/2023 inspection. System is given approval for continued operation as a two bedroom system. Any future alterations or additions will require an OWTS evaluation. [Christopher Peters @ 03/28/2025 12:47 PM]
Fire Code Review
Approved
03/28/2025
03/26/2025
Reviewer:
Reviewer Comments:
New site plan was submitted 3-21-2025. Middleton did a site visit on 3-26-2025 and met with the owner. The the turnaround will fit on the site. Vegetation will have to be removed and gravel will have to be bought in to meet fire access standards. Visit Fire Prevention, on www.steamboatsprings.net for details. Fire needs to do a driveway inspection before CO sign-off. [Mike Middleton @ 03/26/2025 4:55 PM]
Planning Review
Approved
03/28/2025
03/24/2025
Reviewer:
Reviewer Comments:
Prior to CO/CA a final inspection is needed to verify chicken coop has been moved out of the setback, Green House has been moved out of the setback, and shed is at or under 120 sq ft [Greg Jaeger @ 03/21/2025 4:21 PM]
Setback- the addition is OK- see above for other structures in setback
Height- OK
Water Body- OK
Skyline- new addition is same height as existing house and on the opposite side of RCR14- no need for a new skyline test
Use- Single Family Dwelling
Size Limit- OK
With conditions attached prior to certificate Planning is OK
Public Works Review
Approved
03/28/2025
03/24/2025
Reviewer:
Reviewer Comments:
Fees
Paid Fees
Amount
Paid
Owing
Date Paid
Steamboat Springs Fire Site Visit/Driveway Inspection
$120.00
$120.00
Paid
03/28/2025
Outstanding Fees
Amount
Paid
Owing
Date Paid
No outstanding fees.
Total Amount Payable Online:
$0.00
Inspections
Inspection
Outcome
Requested
Scheduled
Date Inspected
Framing Inspection
Pending
Inspector:
Wall/Roof Sheeting
Pending
Inspector:
Roofing Inspection
Pending
Inspector:
Insulation Inspection
Pending
Inspector:
Radon Piping
Pending
Inspector:
Shower Pan Inspection
Pending
Inspector:
Drywall Inspection
Pending
Inspector:
Grading Inspection
Pending
Inspector:
Mike Mordi
Send Email
Final Grading Inspection
Pending
Inspector:
Tony Brown
((970) 870-5344)
Send Email
Lath/Veneer Inspection
Pending
Inspector:
Building Final Inspection
Pending
Inspector:
Structural Inspection
Pending
Inspector:
Foundation/Underslab Insulation
Pending
Inspector:
Footing Inspection
Passed
4/9/2025
4/10/2025
04/10/2025
Inspector:
Jeff Yeiser
((970) 870-5371)
Send Email
Foundation Inspection
Passed
4/15/2025
4/16/2025
04/16/2025
Inspector:
Jeff Yeiser
((970) 870-5371)
Send Email
Foundation/Underslab Insulation
Partial Pass
4/22/2025
4/22/2025
04/22/2025
Inspector:
Jeff Yeiser
((970) 870-5371)
Send Email
Foundation Water Proofing
Passed
4/22/2025
4/22/2025
04/22/2025
Inspector:
Jeff Yeiser
((970) 870-5371)
Send Email
Foundation Drain Inspection
Passed
4/22/2025
4/22/2025
04/22/2025
Inspector:
Jeff Yeiser
((970) 870-5371)
Send Email
Conditions
Condition
Status
Category
Miscellaneous
Open
Prior to Issuance of CO/CC
Final Fire Inspection Required
Open
Prior to Issuance of TCO/CO/CC
Related Permit & Planning Applications
There are no related items for this permit application.