Summary

PRAB221072
Accessory Building
Permit(s) Issued
HOME RANCH LLC
New
A-3a - Assembly, churches
A new pavilion and bell tower structure will be constructed on the Home Ranch property which will be used to host a variety of events throughout the year. The pavilion will be constructed with wood purlins bearing on timber trusses which are supported by concrete spread footers. The bell tower will consist of a concrete masonry unit shaft supporting a timber framed roof above.
08/04/2022
09/16/2022
09/16/2025

Locations

Submittals

1 Permit Application Submittal 08/04/2022      Status: Returned for Correction

Review Type Outcome Est. Completion Date Completed
Public Works Review Approved 08/22/2022 08/22/2022
Tony Brown ((970) 870-5344)   Send Email
External Agencies Review Approved 08/22/2022 08/22/2022
Malea Michael-Ferrier ((970) 870-5334)   Send Email
N. Routt Fire - chief@northrouttfire.org No issues or comments...
Building Code Review Failed 08/22/2022 08/16/2022
Ted Allen ((970) 870-5329)   Send Email
Miscellaneous
Carried Forward
08/23/2022


Before the existing lodge building is approved to serve the public for public water closets, lavatories, drinking fountains and service sinks, the kitchen (if applicable) and rest rooms require a change of use from how this facility was last reviewed. Also, the required public facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed a distance of 500 feet (152 m). Provide a floor plan to show that total of water closets, lavatories and service sinks that are to be provided to include provisions for accessibility, as applicable. Include architectural plans showing room uses, dimensions required to verify code requirements, accessibility, accessible route, and location on Site Plan as per IBC 2902.3.3. The adopted IPC Section 311.1 finds toilet facilities of the nonsewer type shall be provided for construction workers and such facilities shall be maintained in a sanitary condition. Family or assisted-use toilet and bathing rooms shall be located on an accessible route as applicable.
Miscellaneous
Carried Forward
08/23/2022


The engineer in responsible charge of the design shall verify in writing if special inspection is required by IBC Section 1704 to include masonry walls. The inspection program shall designate the portions of the work that require special inspection and the name or names of the individuals or firms who are to perform the special inspections, and indicate the duties of the special inspectors. Special inspectors shall be employed by the owner, the architect or engineer responsible for the design, or an agent of the owner, but NOT by the contractor or any other person responsible for the work. Provide the name or names of the individuals or firms who are to perform the special inspections.
GIS Land Development Review Approved 08/22/2022 08/11/2022
Jason Blair ((970) 870-5465)   Send Email
Unique address is not required for pavilion. Proposed structure is located adjacent to existing cabin with the address: 27315 Home Ranch Rd Unit J. Address and Parcel # have been updated on permit to show nearest existing address.
Environmental Health Review Failed 08/22/2022 08/11/2022
Heather Savalox ((970) 870-5588)   Send Email
Facility plans indicate restrooms and a kitchen which require wastewater disposal to an onsite wastewater treatment system. Application materials and fees are located here: https://cityview2.iharriscomputer.com/RouttCountyPortal
Planning Review Approved 08/22/2022 08/08/2022
Michael Fitz ((970) 879-2704)   Send Email
Open-air pavilion proposed on Home Ranch parcel. Pavilion is consistent with PUD plan recorded at Reception #837644.

2 Permit Application Submittal 08/22/2022      Status: Returned for Correction

Review Type Outcome Est. Completion Date Completed
Environmental Health Review Failed 08/30/2022 09/02/2022
Scott Cowman ((970) 870-5401)   Send Email
Building Code Review Failed 08/30/2022 08/26/2022
Ted Allen ((970) 870-5329)   Send Email
Miscellaneous
Carried Forward
09/06/2022


Before the existing lodge building is approved to serve the public for public water closets, lavatories, drinking fountains and service sinks, the kitchen (if applicable) and rest rooms require a change of use from how this facility was last reviewed. Also, the required public facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed a distance of 500 feet (152 m). Provide a floor plan to show that total of water closets, lavatories and service sinks that are to be provided to include provisions for accessibility, as applicable. Include architectural plans showing room uses, dimensions required to verify code requirements, accessibility, accessible route, and location on Site Plan as per IBC 2902.3.3. The adopted IPC Section 311.1 finds toilet facilities of the nonsewer type shall be provided for construction workers and such facilities shall be maintained in a sanitary condition. Family or assisted-use toilet and bathing rooms shall be located on an accessible route as applicable. UNRESOLVED. However RCRBD is authorized to accept proposed modifications and alternative methods of construction where the strict letter of the code is impractical and the modification or alternative method is in compliance with the intent and purpose of the code, alternative materials, designs and methods not specifically addressed in the code can be approved by the building official where the proposed materials, designs or methods comply with the intent of the provisions of the code (see Section 104.11).
Miscellaneous
Carried Forward
09/06/2022


The engineer in responsible charge of the design shall verify in writing if special inspection is required by IBC Section 1704 to include masonry walls. The inspection program shall designate the portions of the work that require special inspection and the name or names of the individuals or firms who are to perform the special inspections, and indicate the duties of the special inspectors. Special inspectors shall be employed by the owner, the architect or engineer responsible for the design, or an agent of the owner, but NOT by the contractor or any other person responsible for the work. Provide the name or names of the individuals or firms who are to perform the special inspections. UNRESOLVED. Please submit the special inspection program as requested.

3 Permit Application Submittal 09/06/2022      Status: Returned for Correction

Review Type Outcome Est. Completion Date Completed
Building Code Review Failed 09/13/2022 09/07/2022
Ted Allen ((970) 870-5329)   Send Email
Miscellaneous
Resolved
09/07/2022


Before the existing lodge building is approved to serve the public for public water closets, lavatories, drinking fountains and service sinks, the kitchen (if applicable) and rest rooms require a change of use from how this facility was last reviewed. Also, the required public facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed a distance of 500 feet (152 m). Provide a floor plan to show that total of water closets, lavatories and service sinks that are to be provided to include provisions for accessibility, as applicable. Include architectural plans showing room uses, dimensions required to verify code requirements, accessibility, accessible route, and location on Site Plan as per IBC 2902.3.3. The adopted IPC Section 311.1 finds toilet facilities of the nonsewer type shall be provided for construction workers and such facilities shall be maintained in a sanitary condition. Family or assisted-use toilet and bathing rooms shall be located on an accessible route as applicable. UNRESOLVED. However RCRBD is authorized to accept proposed modifications and alternative methods of construction where the strict letter of the code is impractical and the modification or alternative method is in compliance with the intent and purpose of the code, alternative materials, designs and methods not specifically addressed in the code can be approved by the building official where the proposed materials, designs or methods comply with the intent of the provisions of the code (see Section 104.11).
Miscellaneous
Resolved
09/15/2022


The engineer in responsible charge of the design shall verify in writing if special inspection is required by IBC Section 1704 to include masonry walls. The inspection program shall designate the portions of the work that require special inspection and the name or names of the individuals or firms who are to perform the special inspections, and indicate the duties of the special inspectors. Special inspectors shall be employed by the owner, the architect or engineer responsible for the design, or an agent of the owner, but NOT by the contractor or any other person responsible for the work. Provide the name or names of the individuals or firms who are to perform the special inspections. UNRESOLVED. Please submit the special inspection program as requested.
Environmental Health Review Approved 09/13/2022 09/06/2022
Amanda Williams ((970) 870-5588)   Send Email
ACCORDING TO THE LETTER SENT BY SNAKE RIVER CONSTRUCTION THE PAVILLION WILL NOT HAVE RESTROOMS PORT O POTTIES WILL BE BROUGHT IN FOR EVNETS. THIS APPROVAL DOES NOT NEGATE THE FAILED REVIEW FOR PRAB220245 THE BATHROOM BUILDING APPLICATION. FURTHER INFORMATION IS REQUIRED FOR THIS PROJECT

4 Permit Application Submittal 09/08/2022      Status: Submittal Accepted

Review Type Outcome Est. Completion Date Completed
Building Code Review Approved 10/27/2022 10/21/2022
Ted Allen ((970) 870-5329)   Send Email
Addendum 10.20.22
Building Code Review Approved 09/19/2022 09/15/2022
Ted Allen ((970) 870-5329)   Send Email
Miscellaneous
Resolved
09/15/2022


The engineer in responsible charge of the design shall verify in writing if special inspection is required by IBC Section 1704 to include masonry walls. The inspection program shall designate the portions of the work that require special inspection and the name or names of the individuals or firms who are to perform the special inspections, and indicate the duties of the special inspectors. Special inspectors shall be employed by the owner, the architect or engineer responsible for the design, or an agent of the owner, but NOT by the contractor or any other person responsible for the work. Provide the name or names of the individuals or firms who are to perform the special inspections. UNRESOLVED. Please submit the special inspection program as requested.

Fees

Paid Fees Amount Paid Owing Date Paid
Routt County Use Tax Fee $2,443.50 $2,443.50 Paid 09/12/2022
Routt County Planning Dept Plan Review Fee $75.00 $75.00 Paid 08/05/2022
Building Permit Fee $2,854.94 $2,854.94 Paid 09/12/2022
Plan Review Fee $1,855.71 $1,855.71 Paid 08/05/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Foundation Drain Inspection Pending
Roofing Inspection Pending
Insulation Inspection Pending
Drywall Inspection Pending
Grading Inspection Pending
Mike Mordi   Send Email
Final Grading Inspection Pending
Tony Brown ((970) 870-5344)   Send Email
Building Final Inspection Pending
Footing Inspection Pending
Framing Inspection Pending
Footing Inspection Not Ready 10/7/2022 10/10/2022 10/10/2022
Silas Ebbert ((970) 870-5347)   Send Email
Footing Inspection Passed 10/11/2022 (AM) 10/12/2022 10/12/2022
Silas Ebbert ((970) 870-5347)   Send Email
Foundation Inspection Passed 10/18/2022 10/17/2022 10/18/2022
Silas Ebbert ((970) 870-5347)   Send Email
Framing Inspection Partial Pass 9/12/2023 9/12/2023 09/12/2023
Ron Norton ((970) 870-5331)   Send Email

Conditions

Condition Status Department Category Expiration Date Due Date
Miscellaneous Open Building Services Prior to Final Building Inspection
: Norwest Colorado Consultants (NWCC) to act on the behalf of the owner as the 3rd party special inspector, who will be responsible for compliance assurance as outlined in letter.

Related Permit & Planning Applications

Reference Number Status Type
PRPL231195 Permit(s) Issued Plumbing
PREL231209 Permit(s) Issued Electrical