You will only be able to schedule inspections if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRSF221403
New Single Family Dwelling
Permit(s) Issued
PRATT, ROBERT W & ERIN D (JT)
New
R-3 - Residential, one- and two-family
New Single Family Home With Attached Garage at 26730 County Road 14.
09/29/2022
04/10/2023

Locations

Submittals

1 Permit Application Submittal 09/29/2022      Status: Returned for Correction

Review Type Outcome Est. Completion Date Completed
Building Code Review Failed 10/14/2022 10/12/2022
Malea Michael-Ferrier ((970) 870-5334)   Send Email
See Document Markups
Carried Forward
01/17/2023


The soils report referenced on S1.0 does not match the soils report that was submitted. Please either update the notes on the drawings or submit the soils report that is referenced.
See Document Markups
Carried Forward
01/17/2023


RCBD NOTE: A separate permit must be obtained for the Solar array.
See Document Markups
Carried Forward
01/17/2023


Garage passage door must be 20 minute fire rated door equipped with self-closing or automatic closing device.
See Document Markups
Carried Forward
01/17/2023


Please add the following information to your construction documents: a. Indicate which Energy Code compliance path you are using. b. Indicate which method you will be using to meet the whole house ventilation requirements. c. Please note U-Values on windows and doors. d. Add notes to indicate code compliance with sections R314: Smoke alarms and R315: Carbon monoxide alarms.
See Document Markups
Carried Forward
01/17/2023


Please clearly identify the use of the utility room and if is part of the residence or part of the garage. Add notes for required fire separation that is appropriate to the use and location.
See Document Markups
Carried Forward
01/17/2023


Utility room ceiling must be 1/2" gypsum wallboard or other approved material to comply with section R302.1.3: Fire protection of floors.
See Document Markups
Carried Forward
01/17/2023


Provide information indicating how you will meet the requirements in Appendix F: Radon control measures.
See Document Markups
Carried Forward
01/17/2023


Not less than 5/8" Type X gypsum board must be applied to ceiling and on the garage side of the wall separating the garage from the dwelling.
See Document Markups
Carried Forward
01/17/2023


Please indicate if the garage drain system will be sloped to the outside, interior drain connected to the building sanitary system or internal drain daylighted to the exterior of the building.
See Document Markups
Carried Forward
01/17/2023


Please indication where roof drain is draining to. Please note that the roof drain cannot connect to the perimeter foundation drain.
Miscellaneous
Carried Forward
01/17/2023


Informational notes: a. The mezzanine has been reviewed and meets the code requirements of Section R325 and the ship's ladder is an acceptable means of egress, however, this space cannot be used as a bedroom or sleeping area. b. I have added the following conditions to your permit: Blower Door Test Results must be submitted prior to issuance of Certificate of Occupancy. You must achieve 3 ACH or less to pass. Heat load calculations must be submitted and approved prior to the installation of the HVAC system. c. Separate Electrical, Mechanical and Plumbing permit are required. d. A separate permit for the solar array must be obtained.
Public Works Review Approved 10/14/2022 10/12/2022
Tony Brown ((970) 870-5344)   Send Email
External Agencies Review Approved 10/14/2022 10/10/2022
Malea Michael-Ferrier ((970) 870-5334)   Send Email
YVEA - inspections@yvea.com Meter to be located as described by YVEA. They shall not be enclosed, covered or concealed. Violation shall result in termination of service. This approval addresses only the meter and service location.
Fire Code Review Failed 10/14/2022 10/06/2022
Doug Shaffer ((970) 871-8612)   Send Email
Miscellaneous
Carried Forward
01/17/2023


Resubmittal of site plan required - resubmittal of site plan with access width, grade, turning radius and turnaround meeting Fire Dept. access requirements. If unable to meet requirements, submittal of fire sprinkler and monitored fire alarm plans and permits. No inspections past foundation until the above is resolved. www.steamboatsprings.net for details.
Resubmittal of site plan required - resubmittal of site plan with access width, grade, turning radius and turnaround meeting Fire Dept. access requirements. If unable to meet requirements, submittal of fire sprinkler and monitored fire alarm plans and permits. No inspections past foundation until the above is resolved. www.steamboatsprings.net for details.
GIS Land Development Review Failed 10/14/2022 10/03/2022
Laura Meyers ((970) 870-5464)   Send Email
Site plan is not complete. I am requesting a revised site plan showing all of parcel so address can be confirmed.
Environmental Health Review Failed 10/14/2022 10/03/2022
Amanda Williams ((970) 870-5588)   Send Email
Application, application fee $700.00 as well as OWTS engineered design. Please visit the Routt County website / Environmental Health / Apply for a septic permit / Please call Environmental Health when application is completed, that is how we make the fee payable. Be sure to scroll all the way down to bottom of page for payment. Upload engineered design to Documents and images on your application; this is located in the column on the right https://cityview2.iharriscomputer.com/RouttCountyPortal
Planning Review Failed 10/14/2022 09/30/2022
Michael Fitz ((970) 879-2704)   Send Email
Miscellaneous
Carried Forward
01/17/2023


Site plan is not a full site plan, cannot measure setbacks.
Miscellaneous
Carried Forward
01/17/2023


Existing and Finished grade must be shown on elevation drawings (page A3.1 of the plans). A line of some kind is shown but it is not labelled as either existing or finished, and both must be shown.
Single-family home proposed on AF-zoned Daschle Subd Lot 2. Cannot measure setbacks or height, see Corrections. Skyline/waterbodies/floodplain OK. Informational notes: Geo mapped as Slope Failure Complex and Fire risk mapped as High. A Waterbody Setback permit was previously obtained for this construction to build the driveway.

2 Permit Application Submittal 10/12/2022      Status: Returned for Correction

Review Type Outcome Est. Completion Date Completed
Environmental Health Review Approved 01/24/2023 02/27/2023
Amanda Williams ((970) 870-5588)   Send Email
OWTS
Resolved
02/27/2023


everything has been received
See comment history below. The OWTS fee has increased to $1000.00 as of 1/1/2023. Please upload engineered design as well as site plan to your OWTS application. Once this is completed reach out to me at 970-870-5400 or email. I will make the fee payable and carry on with my review
Fire Code Review Failed 01/24/2023 01/23/2023
Doug Shaffer ((970) 871-8612)   Send Email
Miscellaneous
Carried Forward
02/06/2023


Resubmittal of site plan required - resubmittal of site plan with access width, grade, turning radius and turnaround meeting Fire Dept. access requirements. If unable to meet requirements, submittal of fire sprinkler and monitored fire alarm plans and permits. No inspections past foundation until the above is resolved. www.steamboatsprings.net for details. PLEASE SHOW GRADE% OF DRIVEWAY AND FIRE DEPARTMENT TURNAROUND MW
Resubmittal of site plan required - resubmittal of site plan with access width, grade, turning radius and turnaround meeting Fire Dept. access requirements. If unable to meet requirements, submittal of fire sprinkler and monitored fire alarm plans and permits. No inspections past foundation until the above is resolved. www.steamboatsprings.net for details. PLEASE SHOW GRADE% OF DRIVEWAY AND FIRE DEPARTMENT TURNAROUND MW
Building Code Review Approved 01/24/2023 01/17/2023
Malea Michael-Ferrier ((970) 870-5334)   Send Email
See Document Markups
Resolved
01/17/2023


The soils report referenced on S1.0 does not match the soils report that was submitted. Please either update the notes on the drawings or submit the soils report that is referenced.
See Document Markups
Resolved
01/17/2023


RCBD NOTE: A separate permit must be obtained for the Solar array.
See Document Markups
Resolved
01/17/2023


Garage passage door must be 20 minute fire rated door equipped with self-closing or automatic closing device.
See Document Markups
Resolved
01/17/2023


Please add the following information to your construction documents: a. Indicate which Energy Code compliance path you are using. b. Indicate which method you will be using to meet the whole house ventilation requirements. c. Please note U-Values on windows and doors. d. Add notes to indicate code compliance with sections R314: Smoke alarms and R315: Carbon monoxide alarms.
See Document Markups
Resolved
01/17/2023


Please clearly identify the use of the utility room and if is part of the residence or part of the garage. Add notes for required fire separation that is appropriate to the use and location.
See Document Markups
Resolved
01/17/2023


Utility room ceiling must be 1/2" gypsum wallboard or other approved material to comply with section R302.1.3: Fire protection of floors.
See Document Markups
Resolved
01/17/2023


Provide information indicating how you will meet the requirements in Appendix F: Radon control measures.
See Document Markups
Resolved
01/17/2023


Not less than 5/8" Type X gypsum board must be applied to ceiling and on the garage side of the wall separating the garage from the dwelling.
See Document Markups
Resolved
01/17/2023


Please indicate if the garage drain system will be sloped to the outside, interior drain connected to the building sanitary system or internal drain daylighted to the exterior of the building.
See Document Markups
Resolved
01/17/2023


Please indication where roof drain is draining to. Please note that the roof drain cannot connect to the perimeter foundation drain.
Miscellaneous
Resolved
01/17/2023


Informational notes: a. The mezzanine has been reviewed and meets the code requirements of Section R325 and the ship's ladder is an acceptable means of egress, however, this space cannot be used as a bedroom or sleeping area. b. I have added the following conditions to your permit: Blower Door Test Results must be submitted prior to issuance of Certificate of Occupancy. You must achieve 3 ACH or less to pass. Heat load calculations must be submitted and approved prior to the installation of the HVAC system. c. Separate Electrical, Mechanical and Plumbing permit are required. d. A separate permit for the solar array must be obtained.
Planning Review Approved 01/24/2023 01/17/2023
Michael Fitz ((970) 879-2704)   Send Email
Miscellaneous
Resolved
01/17/2023


Site plan is not a full site plan, cannot measure setbacks.
Miscellaneous
Resolved
01/17/2023


Existing and Finished grade must be shown on elevation drawings (page A3.1 of the plans). A line of some kind is shown but it is not labelled as either existing or finished, and both must be shown.
Setback and heights are compliant per revised drawings.
GIS Land Development Review Approved 01/24/2023 01/17/2023
Laura Meyers ((970) 870-5464)   Send Email
Address okay.

3 Permit Application Submittal 01/24/2023      Status: Pending

Review Type Outcome Est. Completion Date Completed
Fire Code Review Approved 02/13/2023 02/06/2023
Doug Shaffer ((970) 871-8612)   Send Email
Miscellaneous
Outstanding
02/06/2023


Resubmittal of site plan required - resubmittal of site plan with access width, grade, turning radius and turnaround meeting Fire Dept. access requirements. If unable to meet requirements, submittal of fire sprinkler and monitored fire alarm plans and permits. No inspections past foundation until the above is resolved. www.steamboatsprings.net for details. PLEASE SHOW GRADE% OF DRIVEWAY AND FIRE DEPARTMENT TURNAROUND MW
full permit MW

Fees

Paid Fees Amount Paid Owing Date Paid
Routt County Planning Dept Plan Review Fee $75.00 $75.00 Paid 09/29/2022
Steamboat Springs Fire Department: Plan Review Fee $25.00 $25.00 Paid 04/10/2023
Routt County Use Tax Fee $10,000.00 $10,000.00 Paid 04/10/2023
Building Permit Fee $7,515.38 $7,515.38 Paid 04/10/2023
Plan Review Fee $4,885.00 $4,885.00 Paid 09/29/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Shower Pan Inspection Pending
Footing Inspection Pending
Roofing Inspection Pending
Insulation Inspection Pending
Drywall Inspection Pending
Grading Inspection Pending
Mike Mordi   Send Email
Final Grading Inspection Pending
Tony Brown ((970) 870-5344)   Send Email
Building Final Inspection Pending
Structural Inspection Pending
Lath/Veneer Inspection Pending
Foundation Inspection Pending
Framing Inspection Pending 5/20/2024 5/20/2024
Foundation Drain Inspection Passed 5/15/2023 5/15/2023 05/15/2023
Jeff Yeiser ((970) 870-5371)   Send Email
Foundation Inspection Partial Pass 5/30/2023 5/30/2023 05/30/2023
Jeff Yeiser ((970) 870-5371)   Send Email
Foundation Inspection Partial Pass 5/31/2023 5/31/2023 05/31/2023
Jeff Yeiser ((970) 870-5371)   Send Email
Radon Piping Passed 7/19/2023 7/19/2023 07/19/2023
Jeff Yeiser ((970) 870-5371)   Send Email
Foundation/Underslab Insulation Passed 7/27/2023 7/27/2023 07/27/2023
Ron Norton ((970) 870-5331)   Send Email
Foundation Water Proofing Passed 7/27/2023 7/27/2023 07/27/2023
Jeff Yeiser ((970) 870-5371)   Send Email
Wall/Roof Sheeting Passed 5/17/2024 05/17/2024
Jeff Yeiser ((970) 870-5371)   Send Email

Conditions

Condition Status Department Category Expiration Date Due Date
Design Engineer on-site Wastewater final report Open Environmental Health Prior to Issuance of CO/CC
: Design Engineer on-site Wastewater final report, including as Built plans.
Blower door test results Open Building Services Prior to Issuance of CO/CC
: Blower Door Test Results
Heat Loss Calculations Deferred Submittal Open Building Services Prior to Mechanical Permit Issuance for Heat
: Heal Load Calculations must be submitted, reviewed and approved prior to any heating equipment being installed.

Related Permit & Planning Applications

Reference Number Status Type
PRSP230060 Permit(s) Issued On-Site Wastewater
PREL230406 Permit(s) Issued Electrical
PREL230552 Canceled Electrical
PRPL230599 Permit(s) Issued Plumbing
PRPL230827 Permit(s) Issued Plumbing
PRMH230831 Permit(s) Issued Mechanical
PRMH240046 Permit(s) Issued Mechanical

Documents & Images