Permit Application Status
PRAD220010
You will only be able to schedule inspections if you are a contact on the permit application.
Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.
Summary
Property Owner's Full Name:
Locations
Submittals
1 Permit Application Submittal 01/06/2022
Status: Returned for Correction
Documents Returned For Corrections
Review Type
Outcome
Est. Completion Date
Completed
External Agencies Review
Approved
01/24/2022
01/24/2022
Reviewer:
Reviewer Comments:
Electrical Review
Approved
01/24/2022
01/24/2022
Reviewer:
Reviewer Comments:
final approval subject to field inspection
Building Code Review
TCO Approved
01/24/2022
01/21/2022
Reviewer:
Corrections:
Correction 1:
See Document Markups
Comments:
The shop shown on the Site Plan Sheet C-1 appeared as a proposed shop on permit CB-15-008. Please submit permit number constructed under (if known) or open new permit if constructed without permit.
Correction 2:
See Document Markups
Comments:
One of the various plan review duties is to determine the code compliance method or alternative used, appropriate use group and occupancy, type of construction and number occupants and maintain this in a data base. For example, the original Steamboat Lake Outfitters as evidenced by a Certificate of Approval was a retail store with residence on the 2-story of Type V-N construction (C-99-197). When Hahn's Peak Roadhouse opened permit CB-15-008 to enclose the porch the store shared the ground floor with a restaurant of 143 occupants in the commercial area, however only one rough inspection showing two exterior non-load bearing walls were constructed and no certificate was issued. For this permit, the plan submittal shows the north end of the east porch as if a wall closed it (without the proposed exit door) and the opposite end appears without an exterior door that would be okay considering the porch to be unheated. However, the restaurant would require a door to separate the porch. Showing the room uses, existing exits (and doors with hardware) and help identifying any proposed corrections of non-conforming conditions is requested at this time.
Correction 3:
See Document Markups
Comments:
Type I hood shown on Sheet A-3 does not appear under this permit. How was the type and capacity evaluated for sizing the makeup air? What type of cooking appliances are served by the hood? What is the capacity of the hood based on the cooking appliance duty classifications (or exception used) defined in the code?Intake openings shall be located not less than 3 feet (914 mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening.Show location and position of sources of contamination (above roof) and how makeup air intake opening locations comply with IMCSection 401.4 with dimensions to include makeup air outlets in the face of the existing hood.
Correction 4:
See Document Markups
Comments:
As RCRBD understands, the new dish room will have a new dishwasher. Please furnish specifications to include needs such as hood (or exception used). Also, the plumbing requirements should appear in the plumbing plan and isometric.
Correction 5:
See Document Markups
Comments:
New grease interceptor shown on Sheet A-3 does not appear specified under this permit. Please specify grease trap and show venting requirements as applicable.
Reviewer Comments:
GIS Land Development Review
Approved
01/24/2022
01/20/2022
Reviewer:
Reviewer Comments:
Environmental Health Review
TCO Approved
01/24/2022
01/13/2022
Reviewer:
Reviewer Comments:
Approved with conditions. Additional dedicated handwashing sink must be included in dishwashing area. An Onsite Wastewater Treatment System(OWTS) repair/remodel permit from Environmental Health is also required to verify new connections. meet regulations.
Planning Review
Approved
01/24/2022
01/10/2022
Reviewer:
Reviewer Comments:
Proposed small dishwashing room addition onto main building on the Hahn's Peak Roadhouse PUD. Technical Correction to PUD allowed under Section 7.4.1 of RCZR to allow for up to 800 sqft of structure area to be added with approval from Planning Director. Planning Director has reviewed and approved 170 sqft dish room addition. Meets all zoning requirements.
2 Permit Application Submittal 01/24/2022
Status: Returned for Correction
Review Type
Outcome
Est. Completion Date
Completed
Environmental Health Review
Approved
02/10/2022
02/09/2022
Reviewer:
Reviewer Comments:
Handwashing sink has been verified. OWTS permit has been submitted. Open hole inspection after instillation to verify pipe and design standards required for final sign off. Contact R Melzer at Routt County Environmental Health.
Building Code Review
TCO Approved
02/10/2022
02/09/2022
Reviewer:
Corrections:
Correction 1:
See Document Markups
Comments:
The shop shown on the Site Plan Sheet C-1 appeared as a proposed shop on permit CB-15-008. Please submit permit number constructed under (if known) or open new permit if constructed without permit. Applicant reply: The new owner has
begun a design of a large shop. The existing shop building can be addressed at the time of this permit as a method for cleaning up the unpermitted building.
Correction 2:
See Document Markups
Comments:
One of the various plan review duties is to determine the code compliance method or alternative used, appropriate use group and occupancy, type of construction and number occupants and maintain this in a data base. For example, the original Steamboat Lake Outfitters as evidenced by a Certificate of Approval was a retail store with residence on the 2-story of Type V-N construction (C-99-197). When Hahn's Peak Roadhouse opened permit CB-15-008 to enclose the porch the store shared the ground floor with a restaurant of 143 occupants in the commercial area, however only one rough inspection showing two exterior non-load bearing walls were constructed and no certificate was issued. For this permit, the plan submittal shows the north end of the east porch as if a wall closed it (without the proposed exit door) and the opposite end appears without an exterior door that would be okay considering the porch to be unheated. However, the restaurant would require a door to separate the porch. Showing the room uses, existing exits (and doors with hardware) and help identifying any proposed corrections of non-conforming conditions is requested at this time.
Correction 3:
See Document Markups
Comments:
Type I hood shown on Sheet A-3 does not appear under this permit, however a new fan is proposed to be added to the exhaust and request is how was the type and capacity evaluated for sizing the makeup air? The type of cooking appliances are served by the hood What is the capacity of the hood based on the cooking appliance of Medium-duty equipment requires 300 cfm/ft and multiplied by the length of hood is typically how required capacity is calculated. Makeup air outlet openings shall be located in the face of the Hood as shown in the email sent. Provide section detailing how makeup air outlet opening locations in the face of the existing hood with dimensions to include spacing of makeup air outlets. Where a Type I hood is installed, the installation of the entire system, including the hood, ducts, exhaust equipment and makeup air system shall comply with the requirements of IMC Sections 506, 507, 508 and 509.. Also since this will be a Type I hood retrofitted with with an approved automatic fire suppression system complying with the International Building Code and International Fire Code associated permits needed are to be coordinated with the Colorado Department of Public Safety, Division of Fire Prevention and Control. (AHJ). Approval and copy of Final Inspection Report shall be submitted to RCRBD prior to issuance of Certificate of Approval.
Correction 4:
See Document Markups
Comments:
As RCRBD understands, the new dish room will have a new dishwasher. Please furnish specifications to include needs such as hood (or exception used). Also, the plumbing requirements should appear in the plumbing plan and isometric.
Correction 5:
See Document Markups
Comments:
New grease interceptor shown on Sheet A-3 does not appear specified under this permit. Please specify grease trap and show venting requirements as applicable.
Correction 6:
Miscellaneous
Comments:
As part of the kitchen remodel, a new Type II exhaust hood shall be installed over the existing pizza oven. As RCRBD understands, the pizza oven was recently added along with a smoker, however the smoker is to be relocated outside, correct? The code relies heavily on product specifications and listings to provide much of the appliance and equipment installation requirements. Similar installations inspected by RCRBD typically involve Type I Hoods, please submit documentation regarding specifications, listings and installation guides. We will also need any structural modifications necessary, send detail as applicable.
Reviewer Comments:
3 Permit Application Submittal 02/09/2022
Status: Pending
Review Type
Outcome
Est. Completion Date
Completed
COO Review - Building Code
Approved
11/04/2022
11/04/2022
Reviewer:
Reviewer Comments:
COO Review - Building Code
TCO Approved
09/14/2022
09/19/2022
Reviewer:
Reviewer Comments:
TCO approved.
COO Review - Environmental Health
Approved
05/27/2022
05/20/2022
Reviewer:
Reviewer Comments:
Pre-operational inspection for Retail food passed. Approved to operate retail food establishment
COO Review - Building Code
Failed
05/27/2022
05/20/2022
Reviewer:
Reviewer Comments:
Need to resolve condition: Internal fire suppression requirements and associated permits needs to be coordinated with the Colorado Department of Public Safety, Division of Fire Prevention and Control. (AHJ). Approval and copy of Final Inspection Report shall be submitted prior to issuance of Certificate of Approval.
Must Pass Final Electrical inspection.
Building Code Review
VOID
03/04/2022
03/03/2022
Reviewer:
Reviewer Comments:
Building Code Review
Approved
03/17/2022
03/03/2022
Reviewer:
Corrections:
Correction 1:
See Document Markups
Comments:
Type I hood shown on Sheet A-3 does not appear under this permit, however a new fan is proposed to be added to the exhaust and request is how was the type and capacity evaluated for sizing the makeup air? The type of cooking appliances are served by the hood What is the capacity of the hood based on the cooking appliance of Medium-duty equipment requires 300 cfm/ft and multiplied by the length of hood is typically how required capacity is calculated. Makeup air outlet openings shall be located in the face of the Hood as shown in the email sent. Provide section detailing how makeup air outlet opening locations in the face of the existing hood with dimensions to include spacing of makeup air outlets. Where a Type I hood is installed, the installation of the entire system, including the hood, ducts, exhaust equipment and makeup air system shall comply with the requirements of IMC Sections 506, 507, 508 and 509.. Also since this will be a Type I hood retrofitted with with an approved automatic fire suppression system complying with the International Building Code and International Fire Code associated permits needed are to be coordinated with the Colorado Department of Public Safety, Division of Fire Prevention and Control. (AHJ). Approval and copy of Final Inspection Report shall be submitted to RCRBD prior to issuance of Certificate of Approval.
Correction 2:
Miscellaneous
Comments:
As part of the kitchen remodel, a new Type II exhaust hood shall be installed over the existing pizza oven. As RCRBD understands, the pizza oven was recently added along with a smoker, however the smoker is to be relocated outside, correct? The code relies heavily on product specifications and listings to provide much of the appliance and equipment installation requirements. Similar installations inspected by RCRBD typically involve Type I Hoods, please submit documentation regarding specifications, listings and installation guides. We will also need any structural modifications necessary, send detail as applicable.
Reviewer Comments:
Todd Carr has reviewed the Code Modification Request Letter, Existing Pizza Over Specifications, and MEP Plans provided on 03/02/2022 and has approved and Stamped these Plans and Documents.
Fees
There are no fees for this permit application, or you are not authorized to view them.
Inspections
Inspection
Outcome
Requested
Scheduled
Date Inspected
Footing Inspection
Passed
3/25/2022 (AM)
3/28/2022
03/28/2022
Inspector:
Silas Ebbert
((970) 870-5347)
Send Email
Foundation Inspection
Passed
3/28/2022
3/29/2022
03/29/2022
Inspector:
Silas Ebbert
((970) 870-5347)
Send Email
Framing Inspection
Not Ready
4/26/2022
4/26/2022
04/26/2022
Inspector:
Silas Ebbert
((970) 870-5347)
Send Email
Framing Inspection
Partial Pass
4/29/2022
4/29/2022
04/29/2022
Inspector:
Silas Ebbert
((970) 870-5347)
Send Email
Framing Inspection
Passed
5/6/2022
5/6/2022
05/06/2022
Inspector:
Silas Ebbert
((970) 870-5347)
Send Email
Insulation Inspection
Passed
5/11/2022
5/11/2022
05/11/2022
Inspector:
Silas Ebbert
((970) 870-5347)
Send Email
Drywall Inspection
Passed
5/12/2022
5/12/2022
05/12/2022
Inspector:
Silas Ebbert
((970) 870-5347)
Send Email
Building Final Inspection
Partial Pass
5/20/2022
5/20/2022
05/20/2022
Inspector:
Ron Norton
((970) 870-5331)
Send Email
Grading Inspection
VOID
05/23/2022
Inspector:
Heidi Spengler
((970) 870-5332)
Send Email
Final Grading Inspection
VOID
05/23/2022
Inspector:
Heidi Spengler
((970) 870-5332)
Send Email
Building Final Inspection
Not Ready
5/23/2022
05/23/2022
Inspector:
Ron Norton
((970) 870-5331)
Send Email
Building Final Inspection
Partial Pass
9/7/2022
09/07/2022
Inspector:
Silas Ebbert
((970) 870-5347)
Send Email
Building Final Inspection
Passed
10/28/2022
10/28/2022
10/28/2022
Inspector:
Silas Ebbert
((970) 870-5347)
Send Email
Conditions
Condition
Status
Category
Design Engineer on-site Wastewater final report
Resolved
Miscellaneous
Resolved
Prior to Issuance of CO/CC
Miscellaneous
Resolved
Prior to Issuance of TCO/CO/CC
Building Department Conditions to be Completed
Resolved
Prior to Issuance of CO/CC
Related Permit & Planning Applications
There are no related items for this permit application.