Summary

PRAD220010
Addition
Closed
JONES OUTPOST HOLDING LLC
Addition
A-2b - Assembly, restaurants, bars, banquet halls
To add a dish room to an existing building and restaurant.
01/06/2022
03/03/2022
03/03/2025
11/04/2022

Locations

Submittals

1 Permit Application Submittal 01/06/2022      Status: Returned for Correction

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
External Agencies Review Approved 01/24/2022 01/24/2022
Malea Michael-Ferrier ((970) 870-5334)   Send Email
Electrical Review Approved 01/24/2022 01/24/2022
Tom Cook ((970) 870-5339)   Send Email
final approval subject to field inspection
Building Code Review TCO Approved 01/24/2022 01/21/2022
Ted Allen ((970) 870-5329)   Send Email
See Document Markups
Carried Forward
02/03/2022


The shop shown on the Site Plan Sheet C-1 appeared as a proposed shop on permit CB-15-008. Please submit permit number constructed under (if known) or open new permit if constructed without permit.
See Document Markups
Carried Forward
02/03/2022


One of the various plan review duties is to determine the code compliance method or alternative used, appropriate use group and occupancy, type of construction and number occupants and maintain this in a data base. For example, the original Steamboat Lake Outfitters as evidenced by a Certificate of Approval was a retail store with residence on the 2-story of Type V-N construction (C-99-197). When Hahn's Peak Roadhouse opened permit CB-15-008 to enclose the porch the store shared the ground floor with a restaurant of 143 occupants in the commercial area, however only one rough inspection showing two exterior non-load bearing walls were constructed and no certificate was issued. For this permit, the plan submittal shows the north end of the east porch as if a wall closed it (without the proposed exit door) and the opposite end appears without an exterior door that would be okay considering the porch to be unheated. However, the restaurant would require a door to separate the porch. Showing the room uses, existing exits (and doors with hardware) and help identifying any proposed corrections of non-conforming conditions is requested at this time.
See Document Markups
Carried Forward
02/03/2022


Type I hood shown on Sheet A-3 does not appear under this permit. How was the type and capacity evaluated for sizing the makeup air? What type of cooking appliances are served by the hood? What is the capacity of the hood based on the cooking appliance duty classifications (or exception used) defined in the code?Intake openings shall be located not less than 3 feet (914 mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening.Show location and position of sources of contamination (above roof) and how makeup air intake opening locations comply with IMCSection 401.4 with dimensions to include makeup air outlets in the face of the existing hood.
See Document Markups
Carried Forward
02/03/2022


As RCRBD understands, the new dish room will have a new dishwasher. Please furnish specifications to include needs such as hood (or exception used). Also, the plumbing requirements should appear in the plumbing plan and isometric.
See Document Markups
Carried Forward
02/03/2022


New grease interceptor shown on Sheet A-3 does not appear specified under this permit. Please specify grease trap and show venting requirements as applicable.
GIS Land Development Review Approved 01/24/2022 01/20/2022
Jason Blair ((970) 870-5465)   Send Email
Environmental Health Review TCO Approved 01/24/2022 01/13/2022
Rick Melzer ((970) 870-5588)   Send Email
Approved with conditions. Additional dedicated handwashing sink must be included in dishwashing area. An Onsite Wastewater Treatment System(OWTS) repair/remodel permit from Environmental Health is also required to verify new connections. meet regulations.
Planning Review Approved 01/24/2022 01/10/2022
Tegan Ebbert ((970) 879-2704)   Send Email
Proposed small dishwashing room addition onto main building on the Hahn's Peak Roadhouse PUD. Technical Correction to PUD allowed under Section 7.4.1 of RCZR to allow for up to 800 sqft of structure area to be added with approval from Planning Director. Planning Director has reviewed and approved 170 sqft dish room addition. Meets all zoning requirements.

2 Permit Application Submittal 01/24/2022      Status: Returned for Correction

Review Type Outcome Est. Completion Date Completed
Environmental Health Review Approved 02/10/2022 02/09/2022
Amanda Williams ((970) 870-5588)   Send Email
Handwashing sink has been verified. OWTS permit has been submitted. Open hole inspection after instillation to verify pipe and design standards required for final sign off. Contact R Melzer at Routt County Environmental Health.
Building Code Review TCO Approved 02/10/2022 02/09/2022
Ted Allen ((970) 870-5329)   Send Email
See Document Markups
Resolved
02/08/2022


The shop shown on the Site Plan Sheet C-1 appeared as a proposed shop on permit CB-15-008. Please submit permit number constructed under (if known) or open new permit if constructed without permit. Applicant reply: The new owner has begun a design of a large shop. The existing shop building can be addressed at the time of this permit as a method for cleaning up the unpermitted building.
See Document Markups
Resolved
02/08/2022


One of the various plan review duties is to determine the code compliance method or alternative used, appropriate use group and occupancy, type of construction and number occupants and maintain this in a data base. For example, the original Steamboat Lake Outfitters as evidenced by a Certificate of Approval was a retail store with residence on the 2-story of Type V-N construction (C-99-197). When Hahn's Peak Roadhouse opened permit CB-15-008 to enclose the porch the store shared the ground floor with a restaurant of 143 occupants in the commercial area, however only one rough inspection showing two exterior non-load bearing walls were constructed and no certificate was issued. For this permit, the plan submittal shows the north end of the east porch as if a wall closed it (without the proposed exit door) and the opposite end appears without an exterior door that would be okay considering the porch to be unheated. However, the restaurant would require a door to separate the porch. Showing the room uses, existing exits (and doors with hardware) and help identifying any proposed corrections of non-conforming conditions is requested at this time.
See Document Markups
Carried Forward
03/03/2022


Type I hood shown on Sheet A-3 does not appear under this permit, however a new fan is proposed to be added to the exhaust and request is how was the type and capacity evaluated for sizing the makeup air? The type of cooking appliances are served by the hood What is the capacity of the hood based on the cooking appliance of Medium-duty equipment requires 300 cfm/ft and multiplied by the length of hood is typically how required capacity is calculated. Makeup air outlet openings shall be located in the face of the Hood as shown in the email sent. Provide section detailing how makeup air outlet opening locations in the face of the existing hood with dimensions to include spacing of makeup air outlets. Where a Type I hood is installed, the installation of the entire system, including the hood, ducts, exhaust equipment and makeup air system shall comply with the requirements of IMC Sections 506, 507, 508 and 509.. Also since this will be a Type I hood retrofitted with with an approved automatic fire suppression system complying with the International Building Code and International Fire Code associated permits needed are to be coordinated with the Colorado Department of Public Safety, Division of Fire Prevention and Control. (AHJ). Approval and copy of Final Inspection Report shall be submitted to RCRBD prior to issuance of Certificate of Approval.
See Document Markups
Resolved
02/08/2022


As RCRBD understands, the new dish room will have a new dishwasher. Please furnish specifications to include needs such as hood (or exception used). Also, the plumbing requirements should appear in the plumbing plan and isometric.
See Document Markups
Resolved
02/08/2022


New grease interceptor shown on Sheet A-3 does not appear specified under this permit. Please specify grease trap and show venting requirements as applicable.
Miscellaneous
Carried Forward
03/03/2022


As part of the kitchen remodel, a new Type II exhaust hood shall be installed over the existing pizza oven. As RCRBD understands, the pizza oven was recently added along with a smoker, however the smoker is to be relocated outside, correct? The code relies heavily on product specifications and listings to provide much of the appliance and equipment installation requirements. Similar installations inspected by RCRBD typically involve Type I Hoods, please submit documentation regarding specifications, listings and installation guides. We will also need any structural modifications necessary, send detail as applicable.

3 Permit Application Submittal 02/09/2022      Status: Pending

Review Type Outcome Est. Completion Date Completed
COO Review - Building Code Approved 11/04/2022 11/04/2022
Malea Michael-Ferrier ((970) 870-5334)   Send Email
COO Review - Building Code TCO Approved 09/14/2022 09/19/2022
Heidi Spengler ((970) 870-5332)   Send Email
TCO approved.
COO Review - Environmental Health Approved 05/27/2022 05/20/2022
Rick Melzer ((970) 870-5588)   Send Email
Pre-operational inspection for Retail food passed. Approved to operate retail food establishment
COO Review - Building Code Failed 05/27/2022 05/20/2022
Malea Michael-Ferrier ((970) 870-5334)   Send Email
Need to resolve condition: Internal fire suppression requirements and associated permits needs to be coordinated with the Colorado Department of Public Safety, Division of Fire Prevention and Control. (AHJ). Approval and copy of Final Inspection Report shall be submitted prior to issuance of Certificate of Approval. Must Pass Final Electrical inspection.
Building Code Review VOID 03/04/2022 03/03/2022
Todd Carr ((970) 870-5330)   Send Email
Building Code Review Approved 03/17/2022 03/03/2022
Todd Carr ((970) 870-5330)   Send Email
See Document Markups
Outstanding
03/03/2022


Type I hood shown on Sheet A-3 does not appear under this permit, however a new fan is proposed to be added to the exhaust and request is how was the type and capacity evaluated for sizing the makeup air? The type of cooking appliances are served by the hood What is the capacity of the hood based on the cooking appliance of Medium-duty equipment requires 300 cfm/ft and multiplied by the length of hood is typically how required capacity is calculated. Makeup air outlet openings shall be located in the face of the Hood as shown in the email sent. Provide section detailing how makeup air outlet opening locations in the face of the existing hood with dimensions to include spacing of makeup air outlets. Where a Type I hood is installed, the installation of the entire system, including the hood, ducts, exhaust equipment and makeup air system shall comply with the requirements of IMC Sections 506, 507, 508 and 509.. Also since this will be a Type I hood retrofitted with with an approved automatic fire suppression system complying with the International Building Code and International Fire Code associated permits needed are to be coordinated with the Colorado Department of Public Safety, Division of Fire Prevention and Control. (AHJ). Approval and copy of Final Inspection Report shall be submitted to RCRBD prior to issuance of Certificate of Approval.
Miscellaneous
Outstanding
03/03/2022


As part of the kitchen remodel, a new Type II exhaust hood shall be installed over the existing pizza oven. As RCRBD understands, the pizza oven was recently added along with a smoker, however the smoker is to be relocated outside, correct? The code relies heavily on product specifications and listings to provide much of the appliance and equipment installation requirements. Similar installations inspected by RCRBD typically involve Type I Hoods, please submit documentation regarding specifications, listings and installation guides. We will also need any structural modifications necessary, send detail as applicable.
Todd Carr has reviewed the Code Modification Request Letter, Existing Pizza Over Specifications, and MEP Plans provided on 03/02/2022 and has approved and Stamped these Plans and Documents.

Fees

Paid Fees Amount Paid Owing Date Paid
Routt County Use Tax Fee $1,616.28 $1,616.28 Paid 03/03/2022
Routt County Planning Dept Plan Review Fee $75.00 $75.00 Paid 01/07/2022
Building Permit Fee $1,322.78 $1,322.78 Paid 03/03/2022
Plan Review Fee $859.81 $859.81 Paid 01/07/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection Passed 3/25/2022 (AM) 3/28/2022 03/28/2022
Silas Ebbert ((970) 870-5347)   Send Email
Foundation Inspection Passed 3/28/2022 3/29/2022 03/29/2022
Silas Ebbert ((970) 870-5347)   Send Email
Framing Inspection Not Ready 4/26/2022 4/26/2022 04/26/2022
Silas Ebbert ((970) 870-5347)   Send Email
Framing Inspection Partial Pass 4/29/2022 4/29/2022 04/29/2022
Silas Ebbert ((970) 870-5347)   Send Email
Framing Inspection Passed 5/6/2022 5/6/2022 05/06/2022
Silas Ebbert ((970) 870-5347)   Send Email
Insulation Inspection Passed 5/11/2022 5/11/2022 05/11/2022
Silas Ebbert ((970) 870-5347)   Send Email
Drywall Inspection Passed 5/12/2022 5/12/2022 05/12/2022
Silas Ebbert ((970) 870-5347)   Send Email
Building Final Inspection Partial Pass 5/20/2022 5/20/2022 05/20/2022
Ron Norton ((970) 870-5331)   Send Email
Grading Inspection VOID 05/23/2022
Heidi Spengler ((970) 870-5332)   Send Email
Final Grading Inspection VOID 05/23/2022
Heidi Spengler ((970) 870-5332)   Send Email
Building Final Inspection Not Ready 5/23/2022 05/23/2022
Ron Norton ((970) 870-5331)   Send Email
Building Final Inspection Partial Pass 9/7/2022 09/07/2022
Silas Ebbert ((970) 870-5347)   Send Email
Building Final Inspection Passed 10/28/2022 10/28/2022 10/28/2022
Silas Ebbert ((970) 870-5347)   Send Email

Conditions

Condition Status Department Category Expiration Date Due Date
Design Engineer on-site Wastewater final report Resolved Environmental Health
: Design Engineer on-site Wastewater final report, including as Built plans. Verification from contractor t0 Environmental Health is adequate.
Miscellaneous Resolved Environmental Health Prior to Issuance of CO/CC
: Additional dedicated handwashing sink must be included in dishwashing area. An Onsite Wastewater Treatment System(OWTS) repair/remodel permit from Environmental Health is also required to verify new connections. Open hole inspection after instillation to verify pipe and design standards required for final sign off. Contact R Melzer at Routt County Environmental Health.
Miscellaneous Resolved Building Services Prior to Issuance of TCO/CO/CC
: Internal fire suppression requirements and associated permits needs to be coordinated with the Colorado Department of Public Safety, Division of Fire Prevention and Control. (AHJ). Approval and copy of Final Inspection Report shall be submitted prior to issuance of Certificate of Approval. Todd Carr Note: They had the existing Ansel system inspected, re-charged and re-used per report provided.
Building Department Conditions to be Completed Resolved Building Services Prior to Issuance of CO/CC
: Building Department Conditions to be Completed: 1-Need to complete guardrail around make up air on back roof. 2 Need to finish install of roofing on back of building.

Related Permit & Planning Applications

There are no related items for this permit application.

Documents & Images

Date Uploaded File Type Name
02/09/2022 Plans Site Plan-C-1 (Received)
03/03/2022 Plans Struct VVR Outpost-F (Received) (Stamped)
01/06/2022 Email Permit Application PRAD220010 60880 CR 129 Unit A
01/07/2022 Receipt Receipt for transaction:2022-000010
01/24/2022 Letter Permit Review Corrections Notice (Generate/Send Correction Notice)
03/03/2022 Letter Grease Int (Received) (Stamped)
03/03/2022 Plans Original SLO Floor Plan (reference only) (Received) (Stamped)
02/09/2022 Letter Permit Review Corrections Notice (Generate/Send Correction Notice)
03/03/2022 Letter PRAD220010 (STAMPED) Code Modification Request (Received)
03/03/2022 Plans (STAMPED)Plumb Mech VVR Outpost 03-02-22 (Received)
03/03/2022 Letter SPRAD210791 Commons Response Letter 02.08.2022 (Received)
03/03/2022 Plans (STMPED)A-0-A-4R (Received)
03/03/2022 Letter Permit - Detailed
03/03/2022 Receipt Receipt for transaction:2022-000136
03/28/2022 Report Inspection Report (Footing Inspection)
03/29/2022 Report Inspection Report (Foundation Inspection)
04/26/2022 Report Inspection Report (Framing Inspection)
04/29/2022 Report Inspection Report (Framing Inspection)
05/06/2022 Report Inspection Report (Framing Inspection)
05/11/2022 Report Inspection Report (Insulation Inspection)
05/12/2022 Report Inspection Report (Drywall Inspection)
05/20/2022 Report Inspection Report (Building Final Inspection)
05/23/2022 Fire Extinguisher Report 2021
05/23/2022 HOOD CLEANING REPORT
05/23/2022 Steamboat Lake Outpost Hood System Report 2022
05/23/2022 Report Inspection Report (Building Final Inspection)
09/07/2022 Report Inspection Report (Building Final Inspection)
09/19/2022 Letter Certificate of Temporary Occupancy
10/28/2022 Report Inspection Report (Building Final Inspection)
11/04/2022 Other Certificate of Occupancy